Boiler and Chiller Rounds: Daily Checks

November 16, 2026
ImmerseLearn trainee wearing a VR headset in front of virtual HVAC equipment with refrigerant coil tubing and a cutaway indoor unit

Boilers and chillers are among the largest machines a building maintenance technician looks after. Daily rounds catch a leak, a drifting temperature, or a low water level before it becomes a no-heat, no-cooling, or safety emergency. This guide covers what a new technician should check, log, and escalate. Always follow your site procedure and the manufacturer's instructions first.

Before you walk the mechanical room

  1. 1. Wear the hearing protection, eye protection, and other PPE your site requires.
  2. 2. Bring the round sheet, or open the inspection work order in the CMMS, so you record readings in the same order every time.
  3. 3. Review yesterday's readings, open alarms, and notes from the last shift.
  4. 4. Know the exits, the emergency shutoffs you are allowed to use, and the procedure for a gas odor or a refrigerant alarm.
  5. 5. Never open panels, close valves, bypass interlocks, or operate controls you are not trained and authorized to use.

If you smell gas or hear a carbon monoxide or refrigerant alarm, leave the room as your emergency procedure requires and report it from a safe location.

What to record in the boiler log

The National Board of Boiler and Pressure Vessel Inspectors recommends logging readings daily for low-pressure heating boilers and at least once per eight-hour shift for high-pressure boilers. A typical log includes:

  1. 1. Which boilers are in service and the fuel in use.
  2. 2. Steam pressure, or water temperature and system pressure on hot-water boilers.
  3. 3. Water level on steam boilers, noted as normal, low, or high.
  4. 4. Operating hours or cycles, when the controls display them.
  5. 5. Alarms, lockouts, and anything unusual, with the time and your name.

A log full of check marks and no readings is of little use when a problem appears later. Trends are what reveal a fault early.

Daily boiler checks

  1. 1. Confirm the boiler is firing or standing by normally, with no unexplained alarms or lockouts.
  2. 2. Compare steam pressure or hot-water temperature with the setpoint and the last log entry.
  3. 3. On steam boilers, confirm water is visible in the gauge glass and in the normal range. If no water is visible, shut the boiler down according to your site procedure and do not add water until a safe level has been determined.
  4. 4. Look for leaks at valves, pumps, fittings, and the safety valve discharge pipe.
  5. 5. Confirm combustion air openings are clear and circulating pumps are running.
  6. 6. Log readings and abnormal findings before you leave the room.

Never cap or block a safety valve outlet, and never bypass a low-water cutoff, pressure control, or flame safeguard. Testing these devices, and resetting a boiler that keeps locking out, belongs to a trained and authorized person. Practice the inspection mindset in our boiler inspection and preventive maintenance micro skill.

Many states require licensed operators, a documented log, or periodic inspections for certain boilers. Follow your site procedure and local rules, and escalate rather than adjusting equipment you are not authorized to run.

Daily chiller checks

  1. 1. Confirm the chiller is running or available as scheduled, with no unexplained alarms.
  2. 2. Record chilled water supply and return temperatures and compare them with the setpoint and the last entry.
  3. 3. Note pressures and temperatures already shown on the controller. Do not attach refrigerant gauges.
  4. 4. Look for oil or water leaks, wet insulation, and new vibration or noise.
  5. 5. On air-cooled chillers, keep condenser coils and fans clear of debris and snow.
  6. 6. On water-cooled chillers, confirm condenser water pumps and the cooling tower are running, with no overflow or dry basin.
First-person ImmerseLearn VR practice holding a refrigeration low-pressure switch at a virtual training workbench

Build these habits with the air cooled chiller maintenance micro skill, then follow the manufacturer's checklist for your machine.

Chiller readings worth logging

Reading What to compare it with
Chilled water supply, return, and delta-T Setpoint and design delta-T, often about 10°F
Condenser water entering and leaving Weather and cooling tower status
Evaporator and condenser approach Start-up report or reading after the last tube cleaning
Oil level and oil pressure Manufacturer range and recent trend

A rising approach at a similar load can point to fouled tubes or low flow. Record the trend and report it. Diagnosis belongs to a qualified chiller technician.

EPA Section 608 certification is required for work that could open the refrigerant circuit, such as attaching gauges or adding refrigerant. A visual walk and reading the display typically do not require it. Our Certified HVAC Associate program includes EPA Section 608 Universal certification.

 

Lockout/tagout during rounds

Most of a round is observation. Once a task moves from looking to servicing, OSHA's lockout/tagout standard and your employer's energy control program apply.

  1. 1. Do not remove guards, open electrical enclosures, or open piping during a round unless you are authorized and following the procedure.
  2. 2. Isolate every energy source, apply your own lock and tag, and verify isolation before work begins.
  3. 3. Stay clear of fans, pumps, and boilers in automatic. They can start on their own.
ImmerseLearn VR simulation of an outdoor condensing unit with its electrical compartment open, showing the control board and wiring

Practice the sequence in our lockout/tagout procedure micro skill.

Warning signs to escalate right away

  1. 1. Water, steam, oil, or refrigerant leaking, or a safety valve discharging.
  2. 2. No visible water in a steam boiler gauge glass.
  3. 3. Repeated lockouts, a rumble on light-off, or a burner that will not stay lit.
  4. 4. A burning smell, smoke, or a gas, carbon monoxide, or refrigerant alarm.
  5. 5. Readings far from normal that are still moving the wrong way.

Report what you saw, the last normal reading, and whether the equipment is still running. For where rounds fit a wider routine, see our commercial building preventive maintenance checklist and our guide to facility maintenance technicians and HVAC technicians.

Career services and job placement after you graduate

Finishing training is only the first step. ImmerseLearn graduates get resume help, interview preparation, and job placement support through our employer partner network. Learn more on our Career Services page.

FAQs

What are boiler and chiller rounds?

Rounds are scheduled walks through the mechanical room to look, listen, and record readings on heating and cooling equipment. They catch leaks, alarms, and drifting readings before they become failures.

How often should rounds be done?

Your site procedure and local boiler rules set the frequency. Many buildings do rounds at least once a day or once per shift. The National Board suggests daily log readings for low-pressure heating boilers and at least once per eight-hour shift for high-pressure boilers.

Should a new technician adjust boiler or chiller settings?

Only if you are trained and authorized. New technicians usually observe, record, and escalate abnormal readings to a lead technician, a licensed operator, or the service contractor.

Do I need EPA Section 608 certification to do chiller rounds?

Usually not for a visual round that only reads values shown on the controller. EPA Section 608 certification is required for work that could open the refrigerant circuit, such as attaching gauges or adding refrigerant. ImmerseLearn's Certified HVAC Associate program includes EPA Section 608 Universal certification.